CORRECT STORAGE OF HAZARDOUS MATERIALS (German legislation)

 

An excerpt from the German Federal Water Act ("WHG" §19) - Any work facilities dealing with materials that pose a potential threat to ground water i.e. storage, filling, production, treatment or use of any such products must be designed and equipped to avoid polluting water or have any other detrimental effect on its characteristics.

 

 Construction Approval 
 Our retention basins are manufactured in
 accordance with "StawaR" - the German
 technical requirements for retention basins made
 of steel. Any retention basin that deviates from
 these requirements is covered by one of our
 general construction approvals issued by the
 DIBt (German Institute for Technical 
 Construction)

 

 

 Retention Volume 
 A retention basin must be able to retain the
 volume of the largest packaging unit or at least
 10% of the total volume stored - whatever the
 greater. NB: in water protection areas the entire
 volume must retained i.e. 100%!

 

 

 

   


 